The most common sizing mistake for pulse power supplies is mixing up average current and peak current — quoting by average, running by peak, and tripping on over-temperature soon after. This article walks through the conversions with concrete numbers.
Inside the supply, power devices carry the peak current during each pulse, so the device rating follows the peak. Heat, however, accumulates with the average current, so the cooling system follows the average. Mixing the two leads either to nuisance trips or to chronic over-heating.
Average current = peak current x duty cycle; peak current required = average current / duty cycle.
| Process (average current) | Duty cycle | Peak required | Note |
|---|---|---|---|
| 100 A | 50% | 200 A | Typical single-pulse plating |
| 100 A | 30% | About 333 A | Lower duty cycle, higher peak |
| 100 A | 10% | 1000 A | Confirm peak capability early |
Process sheets usually quote average current, while "max output" on a datasheet often means peak. Aligning the two before requesting a quote avoids most sizing disputes.
Independent adjustment of frequency, duty cycle and peak current separates a programmable pulse power supply from a basic adjustable unit. Check program steps, timed reversal and RS485 protocols against your line requirements. Compare the adjustable pulse power supply and the precision pulse constant-current source, or browse the pulse power supply category.
Two supplies that both "output pulse current" may be built …
2026-10-28Micro-arc oxidation (MAO) grows a ceramic layer in situ on …
2026-10-28In electrochemical water treatment — electrocoagulation and…
2026-10-28With the same bath and the same deposit, switching from DC …
2026-10-28A freshly installed pulse power supply often fails to match…
2026-10-28A common first question about pulse power supplies: the out…