Rectifier Power Supply / Electric Vehicle Rectifier Power Supply / Lithium Battery Charging Rectifier Power Supply from Jinan Nenghua Electromechanical Equipment Co., Ltd., designed for Rectifier Power Supply and its series applications, with engineering customisation to load profile, process requirements and site conditions.
This series converts three-phase AC into regulated DC and covers three technology routes: thyristor phase control, diode rectification and high-frequency IGBT PWM. The key specifications are output voltage and current accuracy, ripple factor, power factor and harmonic content. Typical applications include electrolysis, electroplating, charging, telecom, data centres and industrial DC busbars.
The unit comprises an input breaker and protection stage, a rectifier transformer or high-frequency isolation transformer, the rectifier or chopper power stage, output filtering, measurement and digital control, and cooling. Phase-controlled models use thyristor phase shift for regulation and are robust against surge; high-frequency models use IGBT chopping or PWM rectification for lower harmonics, higher power factor and much reduced size and weight.
For the surge loads and frequent start-stop duty typical of Rectifier Power Supply, soft start, current limiting and overload recovery are specifically tuned to avoid nuisance tripping.
Every unit is full-load burned in and waveform tested before dispatch, with a test report and wiring diagram supplied for acceptance and maintenance.
The basic phase-controlled relationship is Ud = Ud0·cosα, where Ud0 is the ideal no-load DC voltage at zero firing angle and α is the firing delay angle. Output is regulated continuously by changing α, at the cost of reduced power factor and increased harmonics at deep retard. In practice an on-load tap changer is combined with phase control so that α stays within a shallow 10°–30° window, balancing regulation range and power quality.
The pulse number determines harmonic behaviour. A six-pulse rectifier produces characteristic grid harmonics of the 5th, 7th, 11th and 13th order with a current THD typically of 25%–30%. A twelve-pulse arrangement uses two transformers with Y/Δ and Y/Y connections shifted by 30°, raising the lowest characteristic orders to the 11th and 13th and reducing THD to 8%–10%. Twenty-four-pulse systems reach 3%–4%. Where limits are strict, passive or active filters are added.
PWM rectification (active front end) uses IGBT switches with a boost inductor and a current loop to shape the grid current into a sinusoid in phase with the voltage. Power factor exceeds 0.99, input current THD is below 5% and energy can flow in both directions. Vienna and T-type three-level topologies reduce device voltage stress and switching loss in medium and high power, and are widely used in data-centre and charging-pile DC busbars.
Output ripple is suppressed by LC or π filters. The ripple factor γ = ΔU/Ud is typically ≤1% for industrial models, ≤0.5% for plating and electrolysis where coating quality is sensitive, and down to 0.1% for precision test applications. Ripple frequency depends on pulse number and switching frequency; the filter inductor is designed at the critical inductance while the capacitor balances ripple current and service life.
Control uses a dual-loop structure with an outer voltage loop and an inner current loop, switching automatically between constant-voltage and constant-current modes. Parallel units use master-slave or droop current sharing with errors below 3%; combined with N+1 redundancy and hot-swap construction, a faulty module can be replaced without shutdown. For protection, IGBTs use desaturation detection for microsecond short-circuit protection, while thyristor stages rely on fast fuses and electronic protection boards.
Thermal design determines whether the unit can run at full load continuously. Air-cooled models use zoned airflow with front-to-rear heatsink layout, fin spacing matched to air velocity to reduce pressure drop. Water-cooled models use a cold plate with independent channels, thermal grease or phase-change material to lower contact resistance, and outlet temperature and flow sensors. Overall thermal resistance is calculated for the worst case of maximum ambient, full load and half-blocked filters.
Wide-bandgap devices significantly shift the power-density boundary. SiC MOSFETs have about ten times the breakdown field of silicon, so the drift layer is thinner and on-resistance lower at the same rating. With switching frequencies above 40 kHz, magnetic components shrink by more than half and efficiency improves by one to two percentage points. The trade-off is higher dv/dt and di/dt, which place stricter demands on gate drivers, busbars and filtering.
Main features:
| Model | Rectifier Power Supply / Electric Vehicle Rectifier Power Supply / Lithium Battery Charging Rectifier Power Supply |
|---|---|
| Category | Rectifier Power Supply series |
| Input | Three-phase 380/400/480/690 V, 50/60 Hz |
| Output DC voltage | 0–1000 V (up to 35 kV on request) |
| Output DC current | 0–50 kA (model dependent) |
| Voltage/current accuracy | ≤0.5% |
| Ripple factor | ≤1% (optionally ≤0.1%) |
| Related ratings | Customized to application (Rectifier Power Supply series) |
| Cooling | Water-cooled / air-cooled by power class |
| Protection | Overvoltage, overcurrent, short circuit, overtemperature, phase loss, interlock |
| Communication | RS485 Modbus / Ethernet / analogue (optional) |
Parameters above are for reference; final specs subject to the technical agreement / order contract. Non-standard customization is available.
Typical applications of Rectifier Power Supply / Electric Vehicle Rectifier Power Supply / Lithium Battery Charging Rectifier Power Supply include:
Determine the output class from the rated load voltage and current, then allow 1.2–1.5 times margin for surge and start-up current. Electrolysis and plating loads run at full load continuously, so 1.3 times continuous capacity is recommended.
Select the pulse number or AFE scheme according to grid harmonic limits: six-pulse for low power and lenient limits, twelve or twenty-four pulse for medium and large electrolysis and metallurgy, and AFE where power factor and regeneration matter.
Confirm monitoring interfaces: 0–10 V or 4–20 mA analogue, RS485 Modbus, Ethernet or Profibus, together with interlock signals and dry contacts for the host system.
Design and testing follow the GB/T 3859 semiconductor converter standard, GB 17625 harmonic limits, GB/T 2423 environmental test series and IEC 61000 immunity requirements; export models additionally meet the relevant CE or UL clauses. Factory tests typically cover insulation resistance and withstand voltage, full-load temperature rise, efficiency and power factor, ripple and regulation accuracy, and protection trip values, with per-unit records kept for traceability.
For projects integrating with an existing control system, confirm the communication protocol details and point list before contract to avoid rework.
Cooling and maintenance: water-cooled models require stable water quality and flow, with periodic cleaning of the plate heat exchanger and strainers, and draining before freezing weather. Air-cooled models need regular cleaning of inlet filters and heatsinks to prevent derating from blocked airflow. After long shutdown, perform an insulation check and low-voltage trial run before returning to service.
Design and testing follow the GB/T 3859 semiconductor converter standard, GB 17625 harmonic limits, GB/T 2423 environmental test series and IEC 61000 immunity requirements; export models additionally meet the relevant CE or UL clauses. Factory tests typically cover insulation resistance and withstand voltage, full-load temperature rise, efficiency and power factor, ripple and regulation accuracy, and protection trip values, with per-unit records kept for traceability.
High altitude and extreme environments impose additional requirements. Above 1000 m the dielectric strength and cooling capability of air both fall, so derating of 5%–10% per additional 1000 m and larger clearances are applied. Low-temperature sites need low-temperature electrolytic capacitors and anti-condensation heaters, while humid sites need conformal coating and condensation control. Outdoor models also require sun, rain, dust and theft protection with cabinet temperature held by air conditioning or heat exchangers.
Correct installation and commissioning directly affect service life. After positioning, the cabinet is levelled and secured, incoming and outgoing cables are checked for phase sequence and polarity, and power cable cross-sections are chosen for both ampacity and permissible voltage drop. Before energising, insulation resistance is measured and short circuits ruled out; the first start uses soft start or low-voltage trial operation to verify bus establishment, fan direction and communication, then loading proceeds gradually with temperature rise recorded.