Domestic Component Power Supply / Outdoor Domestic Component Power Supply / High-Power Domestic Component Power Supply from Jinan Nenghua Electromechanical Equipment Co., Ltd., designed for Domestic Component Power Supply and its series applications, with engineering customisation to load profile, process requirements and site conditions.
This series is a voltage-class family of DC power supplies covering 24 V, 48 V, 110 V and 220 V industrial and power-operation levels, 750 V, 1000 V and 1500 V storage and charging platform levels, and high-voltage DC duties from 3000 V up to 35 kV. Each class carries its own device ratings, insulation distances and topology, with efficiency, ripple, protection and communication tailored to the application.
The unit comprises an input rectifier or PFC stage, an isolated or non-isolated DC/DC stage, output filtering, sensing and digital control, protection and communication, and cooling. Low-voltage high-current models use synchronous rectification and multiphase paralleling to cut conduction loss; high-voltage models use three-level or multilevel structures to reduce device stress; stringent insulation duties use dry-type or oil-immersed construction with partial-discharge control.
For Domestic Component Power Supply site requirements the enclosure separates power, control and cabling compartments, so routine maintenance does not require a full shutdown.
Every unit is full-load burned in and waveform tested before dispatch, with a test report and wiring diagram supplied for acceptance and maintenance.
Voltage class sets device and insulation selection. A 220 V DC bus can use 650 V devices, a 750 V bus typically uses 1200 V devices, and a 1500 V bus uses 1700 V or 3300 V devices with three-level topologies that halve the per-device stress. Each step up in voltage raises creepage distance, clearance and tracking-index requirements, and changes enclosure size and thermal design.
Typical topologies use a two-stage structure of PFC followed by an LLC resonant or phase-shifted full-bridge converter. The front stage shapes the input current into a sinusoid and provides a regulated bus, while the rear stage provides isolation and regulation through a high-frequency transformer. LLC operating near resonance achieves zero-voltage turn-on on the primary and zero-current turn-off on the secondary rectifiers, reaching efficiency above 96%. For medium and high power with wide voltage range, the dual active bridge (DAB) provides bidirectional energy flow and wide regulation through phase-shift control.
The 1500 V DC platform is now mainstream for storage and PV. Compared with 1000 V systems the current is one third lower at the same power, cutting line loss and copper usage. However DC arcs are harder to extinguish, so dedicated DC breakers, fuses and arc-fault detection are mandatory, together with reverse-polarity protection and a visible isolation point for maintenance. SiC devices raise switching frequency to 40–100 kHz, pushing converter efficiency above 98% and shrinking magnetic components.
Ripple, accuracy and dynamic response are the three basic performance metrics. Ripple is set by switching frequency and output filtering, typically ≤1% for industrial models and ≤0.1% for test and research models. Voltage accuracy is typically ±0.5%, reaching ±0.05% in high-precision models. Dynamic response is measured as the recovery time to ±1% after a load step, with fast models below 1 ms.
Protection and monitoring must address overvoltage, overcurrent, short circuit, reverse polarity, insulation degradation and DC arcing. An insulation monitoring device (IMD) injects a low-frequency signal or measures the asymmetry of positive and negative rail voltages to earth. DC breakers must extinguish arcs and break in both directions. Charging and storage systems also need pre-charge circuits to limit inrush and protect bus capacitors.
Thermal design determines whether the unit can run at full load continuously. Air-cooled models use zoned airflow with front-to-rear heatsink layout, fin spacing matched to air velocity to reduce pressure drop. Water-cooled models use a cold plate with independent channels, thermal grease or phase-change material to lower contact resistance, and outlet temperature and flow sensors. Overall thermal resistance is calculated for the worst case of maximum ambient, full load and half-blocked filters.
Design and testing follow the GB/T 3859 semiconductor converter standard, GB 17625 harmonic limits, GB/T 2423 environmental test series and IEC 61000 immunity requirements; export models additionally meet the relevant CE or UL clauses. Factory tests typically cover insulation resistance and withstand voltage, full-load temperature rise, efficiency and power factor, ripple and regulation accuracy, and protection trip values, with per-unit records kept for traceability.
Main features:
| Model | Domestic Component Power Supply / Outdoor Domestic Component Power Supply / High-Power Domestic Component Power Supply |
|---|---|
| Category | Domestic Component Power Supply series |
| Output voltage range | 24 V–35 kV (voltage-class family) |
| Output power | 0.5 kW–2 MW (parallel expandable) |
| Voltage accuracy | ±0.5% (±0.05% optional) |
| Ripple factor | ≤1% (≤0.1% optional) |
| Full-load efficiency | ≥96% (≥98% with SiC) |
| Related ratings | Customized to application (Domestic Component Power Supply series) |
| Cooling | Water-cooled / air-cooled by power class |
| Protection | Overvoltage, overcurrent, short circuit, overtemperature, phase loss, interlock |
| Communication | RS485 Modbus / Ethernet / analogue (optional) |
Parameters above are for reference; final specs subject to the technical agreement / order contract. Non-standard customization is available.
Typical applications of Domestic Component Power Supply / Outdoor Domestic Component Power Supply / High-Power Domestic Component Power Supply include:
Determine voltage class and power from the system bus voltage and maximum current, then check overload and surge capability against the load type (resistive, capacitive, motor or battery).
Determine filtering and control by accuracy requirements: test applications need low ripple and high-resolution sensing, while industrial applications can relax these to reduce cost.
Confirm communication protocols and paralleling requirements: Modbus, CAN, Ethernet and dry-contact alarms, together with current-sharing method and master-slave settings.
High altitude and extreme environments impose additional requirements. Above 1000 m the dielectric strength and cooling capability of air both fall, so derating of 5%–10% per additional 1000 m and larger clearances are applied. Low-temperature sites need low-temperature electrolytic capacitors and anti-condensation heaters, while humid sites need conformal coating and condensation control. Outdoor models also require sun, rain, dust and theft protection with cabinet temperature held by air conditioning or heat exchangers.
When several units are installed together, calculate the total heat dissipation and ventilation of the room, adding exhaust or a chiller if required.
Cooling and maintenance: water-cooled models require stable water quality and flow, with periodic cleaning of the plate heat exchanger and strainers, and draining before freezing weather. Air-cooled models need regular cleaning of inlet filters and heatsinks to prevent derating from blocked airflow. After long shutdown, perform an insulation check and low-voltage trial run before returning to service.
Thermal design determines whether the unit can run at full load continuously. Air-cooled models use zoned airflow with front-to-rear heatsink layout, fin spacing matched to air velocity to reduce pressure drop. Water-cooled models use a cold plate with independent channels, thermal grease or phase-change material to lower contact resistance, and outlet temperature and flow sensors. Overall thermal resistance is calculated for the worst case of maximum ambient, full load and half-blocked filters.
Design and testing follow the GB/T 3859 semiconductor converter standard, GB 17625 harmonic limits, GB/T 2423 environmental test series and IEC 61000 immunity requirements; export models additionally meet the relevant CE or UL clauses. Factory tests typically cover insulation resistance and withstand voltage, full-load temperature rise, efficiency and power factor, ripple and regulation accuracy, and protection trip values, with per-unit records kept for traceability.
Output filtering and ripple control involve a trade-off between size, cost and performance. A larger inductor reduces ripple but slows dynamic response and increases copper loss; a higher switching frequency shrinks the inductor but raises switching loss and EMI. In practice, interleaved multiphase operation raises the effective ripple frequency, LC and pi filters suppress high-frequency components, and low-ESR capacitors at the output improve transient response.