Heating Power Supply / Adjustable Heating Power Supply / Constant-current Heating Power Supply from Jinan Nenghua Electromechanical Equipment Co., Ltd., designed for Heating Power Supply and its series applications, with engineering customisation to load profile, process requirements and site conditions.
This series converts three-phase AC into regulated DC and covers three technology routes: thyristor phase control, diode rectification and high-frequency IGBT PWM. The key specifications are output voltage and current accuracy, ripple factor, power factor and harmonic content. Typical applications include electrolysis, electroplating, charging, telecom, data centres and industrial DC busbars.
The unit comprises an input breaker and protection stage, a rectifier transformer or high-frequency isolation transformer, the rectifier or chopper power stage, output filtering, measurement and digital control, and cooling. Phase-controlled models use thyristor phase shift for regulation and are robust against surge; high-frequency models use IGBT chopping or PWM rectification for lower harmonics, higher power factor and much reduced size and weight.
In practical Heating Power Supply installations the unit must hold its output stable against load impedance variation, ambient temperature swings and continuous duty, so device derating, thermal margin and protection thresholds all carry reserve.
Modular construction allows power units, control boards and fans to be replaced independently, with common spares reducing lifetime maintenance cost.
The basic phase-controlled relationship is Ud = Ud0·cosα, where Ud0 is the ideal no-load DC voltage at zero firing angle and α is the firing delay angle. Output is regulated continuously by changing α, at the cost of reduced power factor and increased harmonics at deep retard. In practice an on-load tap changer is combined with phase control so that α stays within a shallow 10°–30° window, balancing regulation range and power quality.
The pulse number determines harmonic behaviour. A six-pulse rectifier produces characteristic grid harmonics of the 5th, 7th, 11th and 13th order with a current THD typically of 25%–30%. A twelve-pulse arrangement uses two transformers with Y/Δ and Y/Y connections shifted by 30°, raising the lowest characteristic orders to the 11th and 13th and reducing THD to 8%–10%. Twenty-four-pulse systems reach 3%–4%. Where limits are strict, passive or active filters are added.
PWM rectification (active front end) uses IGBT switches with a boost inductor and a current loop to shape the grid current into a sinusoid in phase with the voltage. Power factor exceeds 0.99, input current THD is below 5% and energy can flow in both directions. Vienna and T-type three-level topologies reduce device voltage stress and switching loss in medium and high power, and are widely used in data-centre and charging-pile DC busbars.
Output ripple is suppressed by LC or π filters. The ripple factor γ = ΔU/Ud is typically ≤1% for industrial models, ≤0.5% for plating and electrolysis where coating quality is sensitive, and down to 0.1% for precision test applications. Ripple frequency depends on pulse number and switching frequency; the filter inductor is designed at the critical inductance while the capacitor balances ripple current and service life.
Control uses a dual-loop structure with an outer voltage loop and an inner current loop, switching automatically between constant-voltage and constant-current modes. Parallel units use master-slave or droop current sharing with errors below 3%; combined with N+1 redundancy and hot-swap construction, a faulty module can be replaced without shutdown. For protection, IGBTs use desaturation detection for microsecond short-circuit protection, while thyristor stages rely on fast fuses and electronic protection boards.
The digital control platform uses a DSP for the main control loop and an FPGA for high-speed timing and multi-channel sampling, exchanging data over a parallel bus. Current and voltage are sensed with isolated amplifiers or Hall sensors, whose sampling rate and resolution set the upper limit of loop bandwidth. Voltage and current loop crossover frequencies are set to one third to one fifth of the load time constant, balancing response and stability. Parameters can be read, written and backed up from the host computer for batch replication.
Wide-bandgap devices significantly shift the power-density boundary. SiC MOSFETs have about ten times the breakdown field of silicon, so the drift layer is thinner and on-resistance lower at the same rating. With switching frequencies above 40 kHz, magnetic components shrink by more than half and efficiency improves by one to two percentage points. The trade-off is higher dv/dt and di/dt, which place stricter demands on gate drivers, busbars and filtering.
Main features:
| Model | Heating Power Supply / Adjustable Heating Power Supply / Constant-current Heating Power Supply |
|---|---|
| Category | Heating Power Supply series |
| Input | Three-phase 380/400/480/690 V, 50/60 Hz |
| Output DC voltage | 0–1000 V (up to 35 kV on request) |
| Output DC current | 0–50 kA (model dependent) |
| Voltage/current accuracy | ≤0.5% |
| Ripple factor | ≤1% (optionally ≤0.1%) |
| Related ratings | Customized to application (Heating Power Supply series) |
| Cooling | Water-cooled / air-cooled by power class |
| Protection | Overvoltage, overcurrent, short circuit, overtemperature, phase loss, interlock |
| Communication | RS485 Modbus / Ethernet / analogue (optional) |
Parameters above are for reference; final specs subject to the technical agreement / order contract. Non-standard customization is available.
Typical applications of Heating Power Supply / Adjustable Heating Power Supply / Constant-current Heating Power Supply include:
Determine the output class from the rated load voltage and current, then allow 1.2–1.5 times margin for surge and start-up current. Electrolysis and plating loads run at full load continuously, so 1.3 times continuous capacity is recommended.
Choose the filter type from the process ripple requirement: ≤1% for general industry, ≤0.5% for plating, ≤0.1% for precision testing. Each step up in ripple performance noticeably increases inductor and capacitor size and cost.
Confirm monitoring interfaces: 0–10 V or 4–20 mA analogue, RS485 Modbus, Ethernet or Profibus, together with interlock signals and dry contacts for the host system.
Design and testing follow the GB/T 3859 semiconductor converter standard, GB 17625 harmonic limits, GB/T 2423 environmental test series and IEC 61000 immunity requirements; export models additionally meet the relevant CE or UL clauses. Factory tests typically cover insulation resistance and withstand voltage, full-load temperature rise, efficiency and power factor, ripple and regulation accuracy, and protection trip values, with per-unit records kept for traceability.
For projects integrating with an existing control system, confirm the communication protocol details and point list before contract to avoid rework.
Cooling and maintenance: water-cooled models require stable water quality and flow, with periodic cleaning of the plate heat exchanger and strainers, and draining before freezing weather. Air-cooled models need regular cleaning of inlet filters and heatsinks to prevent derating from blocked airflow. After long shutdown, perform an insulation check and low-voltage trial run before returning to service.
EMC performance depends on the combination of filtering, shielding and grounding. Input common-mode and differential-mode filter networks suppress conducted interference, snubber capacitors and RC networks reduce device dv/dt, and the enclosure uses continuous welding or conductive gaskets to maintain shielding integrity. Grounding follows single-point practice with separate power and signal grounds, shielded layers grounded at one end to avoid ground loops, and twisted shielded signal cables routed separately from power cables.
Correct installation and commissioning directly affect service life. After positioning, the cabinet is levelled and secured, incoming and outgoing cables are checked for phase sequence and polarity, and power cable cross-sections are chosen for both ampacity and permissible voltage drop. Before energising, insulation resistance is measured and short circuits ruled out; the first start uses soft start or low-voltage trial operation to verify bus establishment, fan direction and communication, then loading proceeds gradually with temperature rise recorded.
Input power quality is an often overlooked hidden cost. Phase-controlled rectifiers lose power factor and increase harmonics at large firing angles, requiring reactive compensation and filtering. High-frequency rectifiers correct power factor but also see efficiency and power factor fall at light load. On-load tap changing, staged switching or multi-pulse schemes keep power factor above 0.9, reducing utility penalties and disturbance to other equipment on the same network.